Primary Current Injection Test Set

Primary Current Injection Test Set

Model

PCT Series

Udey PCT series comprises of two units: 1) a control unit and 2) a loading unit. Thus making the tester compact and portable. Four models are available with outputs from 250 A to 3000 A. The control unit offers a current output of 0-10 Volt at 50 Amp or 0-5 Volt at 100 Amp. Additionally, a separate voltage output of 0-250 V AC is available for testing voltage operated relays coils or checking the magnetization characteristics of current transformers.

  • Machine Feature

    • All outputs continuously variable.
    • Built - in crystal time base multi range DIGITAL TIMER.
    • True RMS digital metering of outputs.
    • Compact rugged design - Fully tropicalised.
    • Auto-switch off in all modes of operation.
    • All current outputs fully isolated and distortion free.
    • Suitable for testing thermal devices
    • All controls and metering centralized.
  • Machine Technical Specification

    Model PCT-5 PCT-10 PCT-20 PCT-30
    Supply 240 V AC, 50/60 HZ 240 V AC, 50/60 HZ 240 V AC, 50/60 HZ 240 V AC, 50/60 HZ
    Power 2 kVA 4 kVA 6 kVA 6 kVA
    Output Loading unit 500 A @ 0-4V
    250 A @ 0-8 V
    1000 A @ 0-4V
    500 A @ 0-8V
    2000 A @ 0-3V
    1000 A @ 0-6V
    3000 A @ 0-2 V
    1500 A @ 0-4V
    Output Control unit 100 A @ 0-5 V
    50 A @ 0-10 V
    0-250 V @ 8 A
    100 A @ 0-5 V
    50 A @ 0-10 V
    0-250 V @ 15 A
    100 A @ 0-5 V
    50 A @ 0-10 V
    0-250 V @ 15 A
    100 A @ 0-5 V
    50 A @ 0-10 V
    0-250 V @ 15 A

     

    RATING : 5 Minutes ON / 15 Minutes OFF. Continuous rating does not exceed 50% of the rated output.

    METERING : 1) LED digital Ammeter, CT operated for current outputs.
    2) LED digital Voltmeter for voltage output.
    Accuracy: ± 1% ± 3 counts.

    DIGITAL TIMER : 4 digit, solid state crystal base timer system. Multi range from .0001 to 9999 seconds.
    Accuracy: ± 0.5 % ± 2 counts

    TIMER CONTROL CIRCUITS : The timer automatically starts when the output is initiated and automatically stops when the device under test operates.
    START SIGNAL: Internal.
    STOP SIGNAL : Via-either normally open or normally closed external contacts.

    AUTO-CUT-OFF : Cuts off output on operation of device under test.

    OPERATION : Circuit breaker in input, mains on indicator, contractor controlled push buttons for current output on or off, contact mode selector and reset switch.
    'SET/TEST' switch to set up test current level.

    CONSTRUCTION : Two piece unit. Sheet steel cabinets powder coated and with fold away lifting handles.

    OPTIONAL ACCESSORIES : 1. Low inductance lead set.
    2. Precision grade (0.5%) Analogue meter with Current transformer.

  • Standard Accessories

    • Operating Manual.
    • 2 meter long 3 core mains cable.
    • 2 meter long inter-connecting cable.